7SR11 & 7SR12 Applications Guide
Page 40 of 48
©2017 Siemens Protection Devices Limited
4.2 Quick Logic Applications
4.2.1
Auto-Changeover Scheme Example
INCOMER 1
INCOMER 2
Start On-Load
Change-over
CB1
OPEN
VT1
VT2
CB1
CB2
CB3
BI 1
BO3
V 1
Vx
Start On-Load
Change-over
Busbar 1
Busbar 2
LOADS
LOADS
Panel Enable
Switch
BI 2
Figure 4.2-1 Example Use of Quick Logic
The MV installation illustrated above is fed from two incomers. To limit the substation fault level the busbar is run
with CB3 open. When a fault occurs on one of the incomers it is isolated by the circuit protection. To re-supply the
disconnected loads from the remaining incomer CB3 is closed.
If the line fault occurs on incomer 1 it must be confirmed that CB 1 has opened before CB3 can be closed. The
relay on incomer 1 confirms that a trip has been issued to CB1 (e.g. Binary Output 2), that CB 1 has opened (e.g.
Binary Input 1) and that no current flows in the circuit (e.g. 37-1 = Virtual 1):
Incomer 1 Relay is Configured:
CB1 Open auxiliary switch wired to BI 1
Trip output to CB1 = BO 2
OUTPUT CONFIG>OUTPUT MATRIX:
37-1
=
V1
OUTPUT CONFIG>OUTPUT MATRIX:
E1
=
BO3
CONTROL & LOGIC>QUICK LOGIC:
E1
=
O2.I1.V1
The output from Incomer 1 (Binary Output 3) relay is input to the relay on CB 3 (Binary Input 1). A panel switch
may be used to enable the On-Load Change-over scheme (Binary Input 2). Before Closing CB3 a check may be
made that there is no voltage on busbar 1 (27/59-1 = Virtual 1). CB 3 is closed from Binary Output 3.
CB3 Relay is Configured:
Panel switch (ON-Load Change-over Enabled) wired to BI2
OUTPUT CONFIG>OUTPUT MATRIX:
27/59-1
=
V1
OUTPUT CONFIG>OUTPUT MATRIX:
E1
=
BO3
CONTROL & LOGIC>QUICK LOGIC:
E1
=
I1.I2.V1
If required a time delay can be added to the output using the CONTROL & LOGIC > QUICK LOGIC:
E1
Pickup Delay
setting
.
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......