Chapter 4 - 7SR120 · Data Communications Definitions
© 2017 Siemens Protection Devices Limited
Chapter 4 - Page 71 of 84
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
111 P 3P Max
0,3
2
4
0.000
1000000.000
112 Q 3P Max
0,3
2
4
0.000
1000000.000
115 Isef Primary
0,3
2
4
1.000
10.000
116 Isef Secondary
0,3
2
4
1000.000
0.050
117 Isef Nominal
0,3
2
4
1000.000
0.050
135 CB Total Trip Count
0,3
1
3
1.000
1.000
136 CB Delta Trip Count
0,3
1
3
1.000
1.000
137 CB Count To AR Block
0,3
1
3
1.000
1.000
138 CB Frequent Ops Count
0,3
1
3
1.000
1.000
165 Ia Last Trip
0,3
1
3
1.000
Disabled
166 Ib Last Trip
0,3
1
3
1.000
Disabled
167 Ic Last Trip
0,3
1
3
1.000
Disabled
168 Va Last Trip
0,3
1
3
1.000
Disabled
169 Vb Last Trip
0,3
1
3
1.000
Disabled
170 Vc Last Trip
0,3
1
3
1.000
Disabled
171 In Last Trip
0,3
1
3
1.000
Disabled
172 Ig Last Trip
0,3
1
3
1.000
Disabled
173 Isef Last Trip
0,3
1
3
1.000
Disabled
174 V Phase A Max
0,3
2
4
0.010
100.000
175 V Phase B Max
0,3
2
4
0.010
100.000
176 V Phase C Max
0,3
2
4
0.010
100.000
177 V Phase AB Max
0,3
2
4
0.010
100.000
178 V Phase BC Max
0,3
2
4
0.010
100.000
179 V Phase CA Max
0,3
2
4
0.010
100.000
184 CB Wear A
0,3
1
3
0.000
1000000.000
185 CB Wear B
0,3
1
3
0.000
1000000.000
186 CB Wear C
0,3
1
3
0.000
1000000.000
187 CB Wear A Remaining
0,3
1
3
1.000
1.000
188 CB Wear B Remaining
0,3
1
3
1.000
1.000
189 CB Wear C Remaining
0,3
1
3
1.000
1.000
190 CB Wear Minimum
0,3
1
3
1.000
1.000
192 Freq Last Trip
0,3
5
7
1.000
1.000
196 Frequency Max
0,3
2
4
100.000
1.000
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......