4. Configure the digital output by selecting the parameter and clicking
Edit
.
Enter the meter password if prompted.
Parameter
Value/range
Description
Source
Digital/Boolean
Link this input to the value that drives the
state of the digital output.
If Source is not linked, the digital output state
is driven by the Force ON, Force OFF values.
Force ON
Pulse
Link this input to a pulse that forces the digital
output on for the PulseWidth duration,
regardless of the Source input.
Force OFF
1
Pulse
Link this input to a pulse that forces the digital
output off.
Normal
1
Pulse
Pulsing this input will switch the driver of the
digital output from Force ON to Source.
Polarity
Inverting/non-inverting
Specifies if the signal to the digital port is
inverted or not inverted.
PulseWidth
0 - 2,000,000
Specifies the duration of the pulse, in
seconds. Setting this parameter to 0 sets the
digital output continuously on.
Assigned Port
—
The physical digital output port connection.
Only available ports are shown.
State
Open/Closed/Not
Available
Indicates the status of the digital output.
1
These parameters are only valid when pulse width is set to 0.
Configuring option module digital outputs using ION Setup
You can configure option module digital outputs using ION Setup.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Expansion Module > Option I/O Modules
and select the
module tab that corresponds to the option module with the digital output you
want to configure.
4. Select the digital output channel and click
Edit
. The setup screen for that
digital output is displayed.