5. Set the log depth and log interval as required for your logging needs.
•
Log Interval
: you can change the interval units to seconds, minutes,
hours or days.
•
Log Depth
: You can set the depth in time (seconds, hours, days, etc.) or
the number of records.
NOTE:
For some log types, you only set the log depth (for example,
waveform recorders).
Log Memory
shows the estimated impact of the changes on the total size of
the log and
Log Storage
displays the estimated available log memory on the
meter.
NOTE:
If you receive a message stating that there is not enough memory
when you change a log’s configuration, check the configuration of your
meter’s other logs. You may not have enough RAM, or short-term
memory, to allow for the new configuration. You may need to use ION
Setup Advanced mode to check the detailed configuration of your logs.
6. Click
Finish
.
In some case, you may see a
Next
button instead of
Finish
. In this case, the
next screen allows you to configure the buffer depth for the log. The screen
displays the overall log depth and a field for setting the log buffer depth. It
also shows the impact of the
Buffer Depth
setting to your meter’s short-term
memory (RAM).
7EN05-0390-00
173