Pollution degree
2
Altitude
< 3000 m (9843 ft) above sea level
Location/mounting
Not suitable for wet locations
For indoor use only
Must be permanently connected and fixed
Maximum operating temperature with option modules
Maximum operating temperature
948M2DO6DI
Digital (2 out, 6 in)
948M2AO4AI
Analog (2 out, 4 in)
70 ºC (158 ºF)
0 - 4
0,1
70 ºC (158 ºF)
0
2
60 ºC (140 ºF)
1, 2
2 - 4
LEDs
Energy pulsing LEDs (visible and infrared)
Type
Visible orange, infrared
Wavelength
600 – 609 nm (orange), 825 – 925 nm (infrared)
Maximum pulse rate
10 Hz (100 ms)
Status LEDs (visible)
Type
Bi-color, red/green
EMC (electromagnetic compatibility)
EMC standards
IEC 62052-11, IEC 61326-1, IEC 61000-6-5
Immunity to electrostatic discharge
IEC 61000-4-2
Immunity to radiated fields
IEC 61000-4-3
Immunity to fast transients
IEC 61000-4-4
Immunity to surges
IEC 61000-4-5
Immunity to conducted disturbances
IEC 61000-4-6, IEC 61000-4-16
Immunity to power frequency magnetic
fields
IEC 61000-4-8
Immunity to conducted disturbances, 2
- 150 kHz
CLC/TR 50579
Immunity to voltage dips and
interruptions
IEC 61000-4-11
Immunity to ring waves
IEC 61000-4-12
Conducted and radiated emissions
EN 55011 and EN 55032 Class B, FCC part 15 Class B, ICES-003 Class B
Surge withstand capability (SWC)
IEEE/ANSI C37.90.1
Safety
Safety construction
IEC/EN 61010-1, CAT III, 400 VLN / 690 V LL
UL 61010-1 and CSA-C22.2 No. 61010-1, CATIII, 347 V LN / 600
V LL
IEC/EN 62052-31, Protective Class II
214