storage. If additional CID files are loaded, IEC 61850 functions are deactivated
until the additional files are removed.
NOTE:
IEC 61850 is not supported over IPv6.
You can load the IEC 61850 configuration file and configure the IEC 61850 custom
modules using ION Setup.
Related Topics
Loading an IEC 61850 configuration file using ION Setup
You can load an IEC 61850 configuration (CID) file using ION Setup over an
Ethernet connection.
You must have:
•
The IEC 68150 configuration file stored in a location accessible by ION Setup.
The configuration file is created by customizing the IEC 61850 device (ICD)
file, which can be downloaded from www.usa.siemens.com/pds.
•
FTP access to your meter from the computer running ION Setup.
NOTE:
Your meter can have only one IEC 61850 configuration (CID) file
loaded onto its internal FTP site. If additional CID files are loaded, IEC 61850
functions are deactivated until the additional files are removed.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Communications > 3rd Party Protocols
and select the
IEC
61850
tab.
4. Highlight a parameter and click
Upload
. Navigate to where you stored your
meter’s CID file, select the file, and click
Open
.
Your meter reviews the CID file to determine if it is valid. This process may
take several minutes.
The CID status indicates whether the meter has received and validated an
IEC 61850 CID file and is operating as an IEC 61850 server.
Configuring additional data for IEC 61850 using ION Setup
You can map additional data to IEC 61850 using ION Setup.
You must have a valid IEC 61850 configuration file loaded onto your meter for IEC
61850 functionality, but it is not necessary for configuring additional data.
NOTE:
You can configure additional data at any time, whether or not IEC
61850 is operating on your meter.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Communications > 3rd Party Protocols
and select the
IEC
61850
tab.
4. Select the information type that corresponds to the type of meter information
that you want to add to your IEC 61850 data. Select analog for numeric
information and digital for boolean or binary information. Click
Edit
. The
custom configuration screen is displayed.
5. Select the desired meter value from those available. If the value you want is
not shown, select
Show all available registers
.
7EN05-0390-00
67