period equal to one quarter of the maximum learning duration, learning is
complete; otherwise, the learning period will be the maximum learning duration.
Example: Setpoint learning duration in a stable system
In this example, the learning duration is 30 days. When the system is stable for 7.5
days (one quarter of 30 days) learning is complete.
115%
110%
105%
100%
95%
90%
Percen
ta
ge of nominal
85%
Maximum duration remaining
Stable learning time
Learned swell limit = 110%
Learned sag limit = 87%
Example: Setpoint learning duration in an unstable system
In this example, the learning duration is 30 days. Because the system is not stable
for 7.5 days (one quarter of the 30 days) learning is complete at the end of the
maximum learning duration.
115%
110%
105%
100%
95%
90%
Percenta
ge of
n
ominal
85%
Maximum duration remaining
Stable learning time
Learned swell limit = 115%
Learned sag limit = 87%
See the ION Reference, available from www.usa.siemens.com/pds, for more
information on Sag/Swell, Setpoint and Relative Setpoint modules.
Implementing standard alarm setpoint learning using ION Setup
You can use ION Setup to implement setpoint learning, which analyzes your
power system and recommends settings.
NOTE:
Your meter’s power system must be stable in order to learn valid
setpoint values.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming > Standard
.
NOTE:
You can manually configure setpoint values by selecting the
setpoint and clicking
Edit
.
134
7EN05-0390-00