Before configuring serial parameters, make sure you have a unique unit ID for
your meter and know the serial network settings (protocol, baud rate, parity and
stop bits).
1. Start ION Setup.
2. Open the
Setup Assistant
for your device.
3. Select
Communications
>
Serial Settings
.
4. Select Com1 or Com4 tab, depending on which hardware serial port you are
configuring.
5. Select a setting and then click
Edit
to configure the setting to match your
communications system.
Serial communications settings available using ION Setup
Parameter
Values
Description
Protocol
ION, Modbus RTU,
Modbus Master, DNP
v3.00, EtherGate, GPS:
Truetime/Datum, GPS:
Arbiter, GPS: Arbiter-
Vorne, Factory, None
Sets the communications protocol for your
meter’s RS-485 port
NOTE:
the
NONE
setting stops
communications using this port.
Baud Rate
2400, 4800, 9600, 19200,
38400, 57600, 115200
Sets the data rate, in bits per second
Rx Timeout
0.1–15
Sets the transmit delay (timeout for receiving
an entire message from a device) in seconds
1
Unit ID
1 to 9999
Sets the meter’s unique ID on the RS-485
network
NOTE:
Modbus serial device range 1 to
247
Serial Port
8N1, 8N2, 8E1, 8E2, 8O1,
8O2
Sets the parity and stop bits for the port
RS485 Bias
Off, On
Turns on biasing when mastering devices
over the RS-485 port
1
Only applies to a subset of protocols
Configuring serial communications settings using the webpages
You can use the meter’s webpages to configure your serial communications
settings.
Before configuring serial parameters, make sure you have a unique unit ID for
your meter and know the serial network settings (protocol, baud rate, parity and
stop bits).
1. Connect to your meter’s webpages using the meter’s IPv4 address or its IPv6
link local address, or use self-discovery then double-clicking the meter’s
network icon.
2. Navigate to
Setup > Serial Port
.
3. Enter the appropriate value for the settings.