WARNING
INACCURATE DATA RESULTS
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
•
Do not use data displayed on the display or in software as a substitute for
proper workplace practices or equipment maintenance.
•
Confirm your alarm is properly configured.
Default alarms available on the display
Parameter
1
Description
Over I unbal
Over unbalanced current alarm
Over THD V1
V1 over total harmonic distortion (THD) voltage alarm
Over THD V2
V2 over total harmonic distortion (THD) voltage alarm
Over THD V3
V3 over total harmonic distortion (THD) voltage alarm
Over kW sd
Over kW sliding demand alarm
Over Ia
Ia over current alarm
Over Ib
Ib over current alarm
Over Ic
Ic over current alarm
Over I4
I4 over current alarm
Over V unbal
Over unbalanced voltage alarm
V1 Setpoint
V1 setpoint alarm
V2 Setpoint
V2 setpoint alarm
V3 Setpoint
V3 setpoint alarm
Freq Setpoint
Frequency setpoint alarm
Sag/Swell 1
Voltage sag/swell alarm
Current Sag Ph1
2
Current sag alarms for phase 1
Current Sag Ph2
2
Current sag alarms for phase 2
Current Sag Ph3
2
Current sag alarms for phase 3
4-30 Volt Intrp Ph1
4-30 voltage interruption power quality alarm for phase 1
4-30 Volt Intrp Ph2
4-30 voltage interruption power quality alarm for phase 2
4-30 Volt Intrp Ph3
4-30 voltage interruption power quality alarm for phase 3
Current Swell Ph1
2
Current swell alarms for phase 1
Current Swell Ph2
2
Current swell alarms for phase 2
Current Swell Ph3
2
Current swell alarms for phase 3
1
Any Setpoint or Relative Setpoint module with an event priority greater than or equal to the Low
alarm event priority is also displayed on this screen.
2
Enabling or disabling one phase for each alarm type will enable or disable all phases for that type.
You can only enable or disable alarms using the display. Alarm configuration is
done using ION Setup. Alarms with a priority less than
Low
(
Info Only
or
None
)
are not displayed.
You must configure all the parameters related to the alarm for alarm functions to
operate. For example, for the Over Ia alarm to operate, you must enter the
nominal value and the conditions that define an alarm state, even if the alarm is
shown as Enabled on the Alarm Setup screen.
128
7EN05-0390-00