Digital output (Form A)
Number
4
Type
Form A solid-state
Reference voltage
40 V
Maximum load voltage
30 V AC / 60 V DC
Maximum load current
75 mA
ON resistance
13 – 40 Ω at 25 °C (77 °F)
Signal type
Continuous or pulse
Pulse frequency
≤ 25 Hz
Relay output (Form C)
Number
2
Type
Form C mechanical relay
Maximum load voltage
250 V AC / 30 V DC
Maximum load current
8 A @ 250 V AC
5 A @ 24 V DC
20k cycles (resistive)
Operate time
max: 10 ms
Release time
max: 5 ms
Lifetime
No Load: 10,000,000 operations
Rated Voltage and Load: 50,000 operations
Digital inputs
Number
8
Type
Externally excited, 24 V DC whetting voltage available from the meter
Reference Voltage
40 V
Event timestamp accuracy
± 1 ms
Maximum voltage
30 V AC / 60 V DC
Pulse frequency
≤ 25 Hz
Response time
1 cycle
Minimum pulse width
20 ms
Current draw
ON: ≤ 2.5 mA
OFF: ≤ 0.5 mA
Voltage ON state
4 to 30 V AC / 4 to 60 V DC
Voltage OFF state
0 to 1.4 V AC / 0 to 2.0 V DC
IRIG-B
IRIG-B00x format (unmodulated IRIG-B time code)
Coded expressions 0 to 7 are supported but the year data is not used.
Environmental characteristics
Operating temperature
-25 ºC to 70 ºC (-13 ºF to 158 ºF)
NOTE:
Maximum operating temperature could change based on the quantity and type of attached
option modules. See
Maximum operating temperature with option modules, page 214
.
Storage temperature
-40 °C to 85 °C (-40 °F to 185 °F)
Humidity rating
5% – 95% RH non-condensing
Maximum dewpoint: 37 °C (99 °F)
7EN05-0390-00
213