4. Select the
General
tab and configure the site.
Parameter
Values/Options
Description
Name
-
Ethernet gateway site name
Comm Link
Ethernet
Ethernet communications
Ethernet options
Gateway
Ethernet gateway
communications
Gateway Info: IP Addr
—
IP address of the Ethernet
gateway meter
Gateway Info: Port
7801, 7802, 502
•
7801 for EtherGate
(Com1)
•
7802 for EtherGate
(Com4)
•
502 for Modbus
gateway
5. Click
OK
to create the site.
6. Right-click on your newly created site and select
Insert Item
.
The
New Network Item
dialog appears.
7. Make sure your newly created Ethernet gateway site is selected in
Attach to
.
8. Select
Device
and click
OK
.
The
New Device
dialog appears.
9. Enter the details of your serial device. Click
OK
to add the serial device to
your Ethernet gateway site.
10. Repeat for all the serial devices on the gateway meter.
NOTE:
Use a separate standard Ethernet connection in ION Setup to
connect to and read data from your Ethernet gateway meter.
HTTP
HTTP (HyperText Transfer Protocol) is the standard protocol used by a web
browser to establish communication between a client computer and the meter’s
web server.
You can view the meter’s webpages by entering the meter’s IP address on a web
browser.
HTTP is not a secure communications protocol. To reduce the risk of security
threats and help prevent unauthorized access to the meter and the network,
configure the meter to always use HTTPS (HyperText Transfer Protocol Secure).
The meter uses Ethernet port 80 for HTTP or port 443 for HTTPS.
HTTPS
HTTPS uses Transport Layer Security (TLS) encryption to secure the
communications channel and protect exchanged data between the client and the
server. When configured to use HTTPS, the meter uses the self-signed certificate
installed on its webserver.
Changing HTTP protocol using ION Setup
You can change the protocol setting for accessing the meter webpages.
It is recommended to use
HTTPS
or
HTTPS with HTTP redirect
to avoid
compromising the security of your local network.
1. Start ION Setup.
58
7EN05-0390-00