Display mode indicator is set to normal (NORM) mode.
•
Revenue lock icon indicates a locked state (green and closed).
•
Alarm icon indicates an unacknowledged high priority historic alarm (red
outline bell).
•
All parameter labels and associated parameter data are cleared.
Display screen title bar and display icons are retained.
Auto-scaling feature
Measurement units on the meter display and webpages automatically scale,
depending on the value of PT Primary and CT Primary.
Voltage units are scaled based on the PT Primary value:
PT Primary value
Units or scaling
< 1000
V
1000 to 999,999
kV
Current units are scaled based on the CT Primary value:
CT Primary value
Units or scaling
< 1000
A
1000 to 999,999
kA
Power units are scaled according to the value of (CT Primary x PT Primary x 3):
(CT Primary x PT Primary x 3) value
Units or scaling
< 1,000,000
kW, kVAR or kVA
1,000,000 to 999,999,999
MW, MVAR or MVA
≥ 1,000,000,000
GW, GVAR or GVA
Display screens
Display modes
Your meter has three display modes and provides access to your meter’s setup
screens:
•
Normal Mode Screens (NORM). In Norm mode, your meter automatically
scrolls through a series of customizable display screens. You can add or
remove Norm mode display screens. If there are no Norm mode display
screens, the meter displays a message stating that there are no available
screens. To exit Norm mode, press the home button to access the display
modes selection screen.
•
Alt Display Mode (ALT): In Alt mode, you can navigate to view the different
alternate screens. You cannot modify the default Alt mode display screens,
but you can add custom screens. To exit Alt display mode, select
Normal
Display Mode
to access the display modes selection screen.
•
Test Mode (TEST): In Test mode, you can manually scroll through a series of
default screens. To exit Test mode, press the home button and select
Exit
Test Mode
.
NOTE:
In Test mode, your meter’s billing quantities stop accumulating
and the data is sent to special test mode registers. These registers are
cleared when you exit Test mode.
Access your meter’s setup screens by pressing the home button in NORM, ALT or
TEST mode. To exit the setup screens, press the home button.