Power quality
Power quality instrument (PQI)
IEC 62586-1/2 PQI-A
IEC 61000-4-30 Class A (
U
din
= 230 V)
IEC 61000–4–15 Class F1 (
U
din
= 230 V / 50 Hz, 120 V / 60 Hz)
Voltage unbalance (
U
nb
)
IEC 61557-12 Class 0.2
Voltage harmonics (
U
h
)
IEC 61557-12 Class 1
Voltage THD (
THD
u
)
IEC 61557-12 Class 1
Current harmonics (
I
h
)
IEC 61557-12 Class 1
Current THD (
THD
i
)
IEC 61557-12 Class 1
Waveform capture
16 - 1024 cycles per sample
Voltage inputs
Specified accuracy range
57 to 400 V L-N / 100 to 690 V L-L (Wye) or 100 to 600 V L-L (Delta or Wye with unearthed
neutral)
Specified accuracy frequency
50/60 Hz ± 15%, 400 Hz ± 10%
Overload
600 V L-N or 1035 V L-L
Impedance
> 5 MΩ
Measurement category
III
Current inputs
Nominal
IEC: 1A / 5A (Class 0.1 S)
ANSI: Current Class 2, 10, 20 (Accuracy Class 0.1)
Specified accuracy current range
10 mA – 20 A
Starting current
1 mA
Withstand
30 A continuous, 50 A @ 10 sec/hr, 500 A @ 1 sec/hr
Impedance
0.3 mΩ (typical)
Burden
0.01 VA max at 5 A
Control power
AC control power
Operating range
50/60 Hz ± 10%: 90 to 480 V ± 10%
400 Hz: 90 to 120 V ± 10%
Burden (meter only)
max: 16.5 W / 38 VA @ 480 V (45 – 65 Hz)
max: 13 W / 24 VA @ 120 V (400 Hz)
Burden (fully optioned meter)
max: 40 W / 80 VA @ 480 V (45 – 65 Hz)
max. 36 W / 58 VA @ 120 V (400 Hz)
Ride-through time (no optional
accessories)
100 ms (6 cycles at 60 Hz) typ., 120 V AC
400 ms (24 cycles at 60 Hz) typ., 240 V AC
1200 ms (72 cycles at 60 Hz) typ., 480 V AC
DC control power
Operating range
110 to 480 V DC ± 15%
Burden (meter only)
max. 13.5 W at 480 V DC
Burden (fully optioned meter)
37 W at 480 V DC
Overvoltage category
III
212
7EN05-0390-00