Installation and commissioning
Before exiting the Setup Assistant, ION Setup performs a meter configuration test
and displays the results. You can review the results and make changes as
needed.
To turn off the meter configuration test:
1. Click
Tools > Options
.
2. Click the Assistant tab and clear the
Configuration Checklist
check box.
NOTE:
ION Setup also performs a configuration test and displays results
when configuring certain features such as the Sag/Swell or Transient Logging
wizard in the Power Quality setup assistant.
Configure basic metering parameters
Use ION Setup’s Metering setup assistant to configure the meter’s basic metering
functionality.
1. Start ION Setup then open the Setup assistant for your meter.
2. Configure the parameters in
Metering Setup > Basic
.
Basic tab
Parameter
Values
Description
Volts Mode
4W-WYE, DELTA,
3W-WYE, SINGLE,
DEMO
Power system type (note DEMO is
demonstration mode only, and does not
use the meter input terminals to display
values)
PT Prim
1 to 999,999
Potential transformer's primary winding
voltage rating
PT Sec
1 to 999,999
Potential transformer's secondary
winding voltage rating
CT Primary
1 to 999,999
Current transformer's primary winding
current rating
CT Secondary
1 to 999,999
Current transformer's secondary winding
current rating
Nominal Voltage
1 to 999,999
Nominal voltage (V) used for metering
functions such as harmonic calculations
and sag/swell detection
Nominal Current
1 to 999,999
Nominal current (A) used for metering
functions such as harmonic calculations
and sag/swell detection
Nominal Frequency
50, 60
Nominal frequency (Hz) used for
metering functions such as alarms
24