Disabling and enabling alarms using the display
You can disable alarms using the meter’s display when you are performing
maintenance tasks on your system and want to prevent nuisance alarms.
NOTE:
To stop an alarm from being displayed without impacting other
metering features, set the alarm priority to
Info Only
.
1. Press the
Home
button on the display.
2. Navigate to
Setup Menu > Alarm Setup
.
3. Press Select.
4. Press Edit. Enter your meter’s password, if prompted.
5. Press the up or down icons to navigate alarms. A gray bar appears behind the
active selection.
6. To select the item(s):
– Press Select for Enable/Disable, or
– Press the up and down icons simultaneously.
7. Press Select to accept the change.
8. Press Select to confirm.
9. Complete the system maintenance tasks.
10. Enable the alarms you disabled.
Related Topics
Meter setup using your display
Configuring setpoint/standard alarms using ION Setup
You can use ION Setup to configure the standard alarm settings.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming
and click the
Standard
tab.
4. Select a setpoint and click
Edit
.
5. Enter the password and click
OK
, if required.
The
Setpoint Setup
screen is displayed.
6. Configure the setpoint values as required.