7.1.2
WiMag Loop Detector Replacement Card : Configuration
Note:
During the first configuration cycle ensure that there is no oward linking to
other cards. This is achieved by temporarily disconnecting the Ethernet connection
from the front of any interface card that links on to a secondard card.
1. Confirm the location
of the ‘configuration design document’
2. Configure the laptop/pc to the same IP address range of the interface card. The
factory default IP address of the interface card is
10.10.10.10
. Subnet mask
255.0.0.0
.(e.g. set the laptop IP address to 10.10.10.9)
3. Connect the PC/laptop to the service port of the WiMag Loop Detector
Replacement Card.
Figure 31 : WiMag Loop Detector Replacement Card