Siemens Mobility Limited
Sopers Lane, Poole, Dorset
BH17 7ER
Version
11
Page 42 of 117
Status
Issued
Last Editor
Jeerh, Manpreet
Date
March 2020
Document
Name
WIMAG GENERAL HANDBOOK
Doc. No.
667/HB/47200/000
Copyright
©
Siemens Mobility Limited 2012. All Rights Reserved.
Figure 27 : Standard Interface Card Configuration Link
4.
Set the ‘new’ IP address of the interface card, as per the configuration sheet.
5.
If required, a ‘Username’ and ‘Password’ may be set. This will be indicated on the
configuration sheet. However, it is generally recommended that username and
password are kept blank.
6. Ensure the interface card is configured to set inputs to permanent detect if link to
Wimag access point timeouts. Ensure the ‘Activate error output’ and ‘Activate
detection zone outputs’ boxes are ticked, and ensure the ‘Timeout’ value is set to
3000 (30s).
Figure 28 : General Settings Screen
7. Set any other settings of the interface card as per the configuration sheet. Any
deviations from the configuration sheet should be recorded on said sheet.