Even when the motor is off, dangerous voltages may be present inside the terminal box used for the
space heater supply or winding energization when the winding is used as heating element.
Motor capacitors will hold a charge even after the power has been cut off. Do not touch the capacitors
and/or motor terminals, before discharging the capacitors completely.
Table 6.3
- Minimum clearance distance (mm) x supply voltage
Voltage
Minimum clearance distance (mm)
U ≤ 440 V
4
440 < U ≤ 690 V
5.5
690 < U ≤ 1000 V
8
1000 < U ≤ 6900 V
45
6900 < U ≤ 11000 V
70
11000 < U ≤ 16500 V
105
If motors are supplied without terminal blocks, insulate the cable terminals with suitable insulation material that
meets the power supply voltage and the insulation class indicated on the motor nameplate.
Ensure correct tightening torque for the power cable and grounding connections as specified in Table 8.7
The clearance distance (see Figure 6.13) between non-insulated live parts with each other and between
grounded parts must be as indicated in Table 6.3.
Clearance distance
Clearance distance
Clearance distance
Clearance distance
Figure 6.13
- Clearance distance representation
Page 158
Summary of Contents for BN 5-12 Series
Page 13: ...TAB 1 DEVICE DATA SHEETS ...
Page 18: ...TAB 2 APPROVED SUBMITTAL ...
Page 23: ...All data subject to change without notice 1 800 ASK 4WEG www weg net 14 ...
Page 26: ...Your advantages our pumps ...
Page 45: ...ADV 2 13E And what can we get flowing for you Your nearest contact Or visit www seepex com ...
Page 117: ...TAB 3 INSTALLATION OPERATIONS AND MAINTENANCE ...
Page 133: ...Page 37 ...
Page 233: ...www weg net Manual of Electric Motors 64 ENGLISH Figure 2 1 IEC motor nameplate Page 135 ...
Page 234: ...www weg net Manual of Electric Motors 65 ENGLISH Figure 2 2 NEMA motor nameplate Page 136 ...
Page 306: ...TAB 4 AS BUILTS AND SUPPLEMENTAL INFORMATION ...
Page 307: ...R Page 29 ...
Page 308: ...R Page 30 ...