Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Overview
Input/output (I/O) modules
6-5
6
6.1.1 Power consumption of PCD2 input/output modules
Type
PCD2.…
Maximum internal
current
consumption
I from +5 V [mA]
Maximum internal
current
consumption
I from V+ [mA]
Maximum external current
consumption
at 24 V, I [mA]
E11x
E16x
E500
E61x
24
72
1
24
--
--
--
--
8 I, 6 mA/I
16 I, 4 mA/I
6 I, 10...12 mA/I
8 I, 5 mA/I
A200/210
A220
A250
A300
A400
A410
A46x
B100
15
20
25
20
25
24
74
25
--
--
--
--
--
--
--
--
32 mA
1)
48 mA
1)
64 mA
1)
Load current
Load current
Load current
Load current
Load current
W200/210
W220
W300/310
W3x5
W340/360
W350
W4x0
W525
W600
W605/625
W610
W615
W720
W745
8
8
8
60
8
8
1
40
4
110
110
55
60
200
5
16
5
--
20
30
30
--
20
--
--
--
100
--
--
--
--
--
--
--
W410 100 mA
2)
Load current
--
--
100 mA
2)
90 mA
--
--
H100/H110
H150
H210
H310/H311
H320/H322
H325/H327
90
25
85
140
230
250
--
--
--
--
20
20
CCO output: Load current
Load current
Load current
max. 15 mA
Load current
Load current
1) Coil resistance of the relay 3 kOhm
2) Basic consumption 20 mA, plus 0...20 mA per output
6.1.2 Capacity of basic units
Unit
internal 5 V-Bus
inV-Bus
PCD2.M5xx0
1,400 mA
200 mA