3.4.3 Extensions with various module holders
The PCD2.M5_ controllers can be expanded with PCD2.C2000/C1000 components,
making additional module sockets available. Up to 7 PCD2.C2000/C1000 module
holders can be connected to the PCD2.M5_ . This allows the user to attach a
maximum of 64 I/O modules, or 1023 digital inputs/outputs.
For local expansion, the PCD2 LIO (local I/O) modules can be used.
For decentralized expansion using Profibus, the PCD3 RIO (remote I/O) modules can
be used:
When selecting I/O modules, ensure that the internal 5V and +V supply is not
overloaded.
The PCD2.M5_ controllers can be expanded with PCD2.C2000/C1000, PCD3.Cxx0
or PCD2.C1x0 components, making additional module sockets available:
PCD2.M5_ type
Maximum number of inputs/outputs or I/O module sockets for the system:
Expansion with
PCD2.C2000/C1000 components
1023
1)2)
64
Expansion with
PCD3.Cxx0 components
1023
1)2)
64
Expansion with
PCD2.C1xx components
255
1)2)
16
1) Using digital I/O modules PCD2/3.E16x or A46x with 16 I/Os each
2) On all PCD2 units, address 255 is reserved for the watchdog. The I/Os reserved for the watchdog cannot be used,
and no analogue and H modules can be used on the sockets with base address 240
Connection cables or plugs required
Type of expansion
PCD2.C150 PCD2.C100 PCD3.C100/.C200
PCD2.C2000/
C1000*
Max. expansion
housings or module
holders
1
1
14
7
Max. plug-in I/O
modules
4
8
56
56
Max. additional digital
I/Os
64
127
895
895
Connecting cable or
PCD2.K1x0
PCD2.K106
PCD3.K1x6
PCD2.K106
PCD3.K1x6
Connector
PCD3.K010
PCD2.K010*
Restrictions
No
No
Max. 6 PCD3.C200
*In preparation