Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
General technical details
PCD2.M5_ Classic CPUs and expansion housings
3-4
3
Noise immunity
acc. to EN61000-6-4
Mechanism and mounting
Housing material
Base:
Cover:
Fibre optics:
PC, crystal-clear
Mounting rail
2 top-hat rails acc. to EN50022-35 (2 x 35 mm)
Connections
Terminal
blocks
Spring
terminals
10-pole,
4-pole
Spring
terminals
10-pole
Spring
terminals
14-pole,
12-pole,
8-pole
Spring
terminals
24-pole,
6-pole
Earth
terminal
Terminal
2-pole
supply
Section
stranded
single wire
0.5..2.5 mm²
0.5..2.5 mm²
0.5..2.5 mm²
0.5..2.5 mm²
0.5...1.5 mm²
0.5...1.5 mm²
0.5...1.0 mm²
0.5...1.0 mm²
0.08...
2.5 mm²
0.5...
1.5 mm²
The terminal blocks may only be plugged onto 20 times. They must then be replaced, to
guarantee a reliable contact
Length of
insulation
7 mm
7 mm
7 mm
7 mm
5...6 mm 7 mm
Standards / approvals
EN/IEC
EN/IEC61131-2 “Programmable controllers”
Shipbuilding
ABS, BV, DNV, GL, LRS, PRS.
Please verify if your chosen product is mentioned in the
list of corresponding Type-Approval-Company under
cULus-listed
Please verify if your chosen product is listed in the corresponding
. The condition for cULus
Compliance are mentioned on the sheet annexed to the product
.