Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
General technical details
PCD2.M5_ Classic CPUs and expansion housings
3-3
3
3.2
General technical details
Supply (external and internal)
Supply voltage
24 V
DC
-20...+25% smoothed or
19 V
AC
±15% full-wave rectified (18V DC)
Power consumption
1)
typically 15 W
Capacity of internal
5 V bus
2)
1,400 mA
Capacity of internal
+V bus (16...24 V)
2)
The capacity of the +V bus depends on the capacity of the 5V
bus, as follows (the more precisely the 24 V are maintained, the
higher the possible capacity):
24 V
24 V
24 V
1) The loads handled by the outputs and other consumers are generally more important for sizing the supply than
the internal power consumption of the PCD2.M5.
2) When planning PCD2 systems, it is essential to check that the two internal supplies are not overloaded. This
check is especially important when using analogue, counter and positioning modules, as these may have a very
large power consumption.
It is advisable to use the “device configurator” from the PG5 2.0 which automatically calculates the internal power
consumption of the modules.
Atmospheric conditions
Ambient temperature
When mounted on vertical surface with vertically aligned
terminals: 0...+55 °C
In all other mounting positions, a reduced temperature range of
0..+40 °C applies
Storage temperature
-25...+85 °C
Relative humidity
10...95 % without condensation
Vibration resistance
Vibration
according to EN/IEC61131-2:
5...13.2 Hz constant amplitude (1.42 mm)
13.2...150 Hz, constant acceleration (1 G)
Electrical safety
Protection type
IP20 according to EN60529
Air/leakage paths
according to EN 61 131-2 and EN50178: between circuits and
bodies and between electrically isolated circuits: surge category
II, fouling level 2
Test voltage
350 V / 50 Hz AC for nominal unit voltage 24 VDC
Electromagnetic compatibility
Electrostatic discharge
according to EN61000-4-2: 8 kV: contact discharge
Electromagnetic fields
according to EN61000-4-3: field intensity 10 V/m,
80...1000 MHz
Bursts
according to EN61000-4-4: 4 kV on DC supply lines, 4 kV on
I/O signal lines, 1 kV on interface lines
Noise emission
according to EN 61,000-4-6: Class A (for industrial areas).
Guidance on the correct use of these controls in residential
areas can be found at www.saia-support.com (additional
measures).