Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Analogue input modules, electrically isolated
Input/output (I/O) modules
6-62
6
Connections
Digital/analogue values
Input signals and type
Digital values
PCD2.W305
PCD2.W315
PCD2.W325
Classic xx7
Simatic
+ 10.0 V
+ 20 mA
+10 V
4095
4095
27684
+ 5.0 V
+ 10 mA
0 V
2047
2047
13842
0 V
0 mA
-10 V
0
0
0
Connection concept for voltage and current inputs
The voltage and current input signals are connected directly to the 14-pole terminal
block (I0…I6 and COM). To minimize the amount of interference coupled into the
module via the transmission lines, connection should be made according to the
principle explained below.