Commissioning
Device bus: receive return temperature 2
If CP 215 is set to 1, the controller receives the return temperature value from the
device bus and uses this instead of its own measurement.
Enabling CP 15 and CP215 simultaneously may be meaningful, both heating
circuits than use the same return temperature measurement that was received on
the device bus.
Device bus: digital room operating unit EDB100 for heating 2
If an EDB100 digital room operating unit is going to be used, CP218 must be set
to 1.
If an EDB100 digital room operating unit is used, the actual value is evaluated for
the room temperature by the EDB100. Measurements from other room operating
units or room sensors ( SP202) are ignored.
Device bus: address of EDB100 digital room operating unit for heating 2
The address of the EDB100 room operating unit assigned to the controller must
be set with CP219.
CP202
CP203
CP204
Summary of Contents for equitherm EQJW245
Page 2: ...2 127 www sauter controls com EQJW245 ...
Page 8: ...8 127 www sauter controls com EQJW245 ...
Page 10: ...10 127 www sauter controls com EQJW245 ...
Page 12: ...12 127 www sauter controls com EQJW245 ...
Page 54: ...54 127 www sauter controls com EQJW245 ...
Page 78: ...78 127 www sauter controls com EQJW245 ...
Page 88: ...88 127 www sauter controls com EQJW245 ...
Page 92: ...92 127 www sauter controls com EQJW245 ...
Page 102: ...102 127 www sauter controls com EQJW245 ...
Page 104: ...104 127 www sauter controls com EQJW245 ...
Page 106: ...106 127 www sauter controls com EQJW245 ...
Page 108: ...108 127 www sauter controls com EQJW245 ...
Page 110: ...110 127 www sauter controls com EQJW245 ...
Page 112: ...112 127 www sauter controls com EQJW245 ...
Page 122: ...122 127 www sauter controls com EQJW245 ...