EQJW245
95/127
www.sauter-controls.com
Using the controller
Control model 2
8.2.2
M
T
T
TF2
TRF2
TRF1
TF1
T
T
(T
)
R1
(T
)
R2
M
PI
UP1
UP2
SP 46
T
TA
T
T
T
T
V1
V2
EQJW245 MOD 2
Fig.10
Weather-compensated fl ow temperature control (secondary) in converter systems
of a direct and a readjusted heating medium circuit (switching in accordance with
AGFW regulation Fig. 3.2.1)
Important SERVice parameters (see also chapter 3.3.4)
SP06
2
(Control model 2)
•
SP07
1
(HK1 in backup mode if binary contact closed)
•
SP08
2
(Room sensor connection with setpoint adjuster for HK 1)
•
SP09
3
(Room temperature activation active for HK2)
•
SP13
1
(Max. return temperature limit for HK1)
•
SP20
40
(Upper return temperature limit for HK1, 2)
•
SP21
40
(Lower return temperature limit for HK1, 2)
•
SP46 5 (Alarm
forwarding)
•
SP200
1
(2nd heating circuit enabled;
•
)
SP201
0
(Binary input, has no infl uence on HK2;
•
)
SP202
2
(Room sensor connection with setpoint adjuster for HK2)
•
SP203
3
(Room temperature activation active for HK2)
•
SP206
1
(Max. return temperature limit for HK2)
•
Summary of Contents for equitherm EQJW245
Page 2: ...2 127 www sauter controls com EQJW245 ...
Page 8: ...8 127 www sauter controls com EQJW245 ...
Page 10: ...10 127 www sauter controls com EQJW245 ...
Page 12: ...12 127 www sauter controls com EQJW245 ...
Page 54: ...54 127 www sauter controls com EQJW245 ...
Page 78: ...78 127 www sauter controls com EQJW245 ...
Page 88: ...88 127 www sauter controls com EQJW245 ...
Page 92: ...92 127 www sauter controls com EQJW245 ...
Page 102: ...102 127 www sauter controls com EQJW245 ...
Page 104: ...104 127 www sauter controls com EQJW245 ...
Page 106: ...106 127 www sauter controls com EQJW245 ...
Page 108: ...108 127 www sauter controls com EQJW245 ...
Page 110: ...110 127 www sauter controls com EQJW245 ...
Page 112: ...112 127 www sauter controls com EQJW245 ...
Page 122: ...122 127 www sauter controls com EQJW245 ...