EQJW245
97/127
www.sauter-controls.com
Using the controller
Control model 4
8.2.4
T
T A
UP 1
T
M
T
T F1
BW
UP 2
LP 1
M
T
T F2
T
PI
(T R2)
T
(T R1)
ZP
KW
T W1
V1
V2
EQJW245 MOD 4
Fig.12
Weather-compensated fl ow temperature control for two heating circuits via
different mixing valves and direct domestic water preparation connection)
Important SERVice parameters (see also chapter 3.3.4)
SP06 4 (Control
model)
•
SP08
1
(Connection of a room sensor for HK1)
•
SP09
3
(Room temperature activation always active for HK1)
•
SP31
1
(domestic water preparation with 1 domestic water sensor)
•
SP33
5
(Switching difference for domestic water preparation;
•
)
SP46
6
(Confi gurable output, used to actuate a circulation pump)
•
SP200
1
(2nd heating circuit enabled;
•
)
SP202
1
(Connection of a room sensor for HK2)
•
SP203
3
(Room temperature activation always active for HK2)
•
Summary of Contents for equitherm EQJW245
Page 2: ...2 127 www sauter controls com EQJW245 ...
Page 8: ...8 127 www sauter controls com EQJW245 ...
Page 10: ...10 127 www sauter controls com EQJW245 ...
Page 12: ...12 127 www sauter controls com EQJW245 ...
Page 54: ...54 127 www sauter controls com EQJW245 ...
Page 78: ...78 127 www sauter controls com EQJW245 ...
Page 88: ...88 127 www sauter controls com EQJW245 ...
Page 92: ...92 127 www sauter controls com EQJW245 ...
Page 102: ...102 127 www sauter controls com EQJW245 ...
Page 104: ...104 127 www sauter controls com EQJW245 ...
Page 106: ...106 127 www sauter controls com EQJW245 ...
Page 108: ...108 127 www sauter controls com EQJW245 ...
Page 110: ...110 127 www sauter controls com EQJW245 ...
Page 112: ...112 127 www sauter controls com EQJW245 ...
Page 122: ...122 127 www sauter controls com EQJW245 ...