82/127
www.sauter-controls.com
EQJW245
Communication functions
Current measured values and operating statuses (for example) can be read out
via Modbus. The controller outputs can be switched. The list of the available data
points is given in the Annexe, Section 6.3.1.
If desired, the controller will monitor the activity of the Modbus interface. As long
as valid Modbus enquiries are registered regularly, the controller will reset the
time monitoring. If no more enquiries are directed to the controller for 30 minutes,
it will operate independently again. Changes to the controller outputs triggered
via Modbus then become invalid. This function can be disabled with CP27.
The EQJW245 is compatible with the ‚Modbus-Frame‘ protocol extension.
Enquiries in standard format are answered in standard format, and frame
enquiries receive an answer in frame format. This format allows reliable data
transmission even if the data are segmented during transmission. For Modbus
communication via modem, it is advisable to use the frame format because
precisely timed data transmission from the sender to the recipient is often not
available with modern transmission methods (modem with compression and
error correction functions, digital telephone network). Details about the protocol
extension are available on request.
6.3.1 Modbus data points (holding register)
Number of
holding
register
Description
Comment
Read
only
Decimal
points
Units
With
math.
Sign?
40001
Product number
Product number, device code
Yes
0
No
40003
Firmware version
Firmware version
Yes
2
No
40004
Hardware version
Hardware version
Yes
2
No
40006
Int. SerNo
Internal serial number
Yes
0
No
40010
OutdoorTemp_AF1
Measured value for input T
A
No
1
°C
Yes
40013
FlowTemp_VF1
Measured value for input T
F
Yes
1
°C
Yes
40014
HotWaterTemp2
Measured value for input T
W2
Yes
1
°C
Yes
40017
ReturnTemp_RüF1
Measured value for input T
RF
Yes
1
°C
Yes
40020
RoomTemp_RF1
Measured value for input T
R
Yes
1
°C
Yes
40023
TankTemp
Measured value for input T
W1
Yes
1
°C
Yes
40100
Time
Time (hours, minutes)
No
2
No
40101
Date
Date (day, month)
No
2
No
40102
Year
Year
No
0
No
40103
Switch position - top
Rotary switch:
0= Position for inputs, 1=Auto, 2=Off,
3=Manual, 4=Normal, 5=Reduced
Yes
0
No
40104
Switch position -
middle
Rotary switch:
0= Position for inputs, 1=Auto, 2=Off,
3=Manual, 4=Day, 5=Night
Yes
0
No
40105
Switch position -
bottom
Rotary switch:
0= Position for inputs, 1=Auto, 2=Off,
3=Manual, 4=Normal, 5=Reduced
Yes
0
No
40106
Mode_Rk1
1=Auto, 2=Stdby, 3=Manual, 4=Sun,
5=Moon
No
0
No
40107
ControlSignal_Rk1
Opening for control signal Rk1 [0 to
100%]
No
0
%
No
Summary of Contents for equitherm EQJW245
Page 2: ...2 127 www sauter controls com EQJW245 ...
Page 8: ...8 127 www sauter controls com EQJW245 ...
Page 10: ...10 127 www sauter controls com EQJW245 ...
Page 12: ...12 127 www sauter controls com EQJW245 ...
Page 54: ...54 127 www sauter controls com EQJW245 ...
Page 78: ...78 127 www sauter controls com EQJW245 ...
Page 88: ...88 127 www sauter controls com EQJW245 ...
Page 92: ...92 127 www sauter controls com EQJW245 ...
Page 102: ...102 127 www sauter controls com EQJW245 ...
Page 104: ...104 127 www sauter controls com EQJW245 ...
Page 106: ...106 127 www sauter controls com EQJW245 ...
Page 108: ...108 127 www sauter controls com EQJW245 ...
Page 110: ...110 127 www sauter controls com EQJW245 ...
Page 112: ...112 127 www sauter controls com EQJW245 ...
Page 122: ...122 127 www sauter controls com EQJW245 ...