86/127
www.sauter-controls.com
EQJW245
these level bits are set again after a timeout period of 30 minutes (unless this
timeout function was disabled in CP27). From then on, the controller resumes
control of all functions.
Modem operation
6.4
A modem of type KT DataMod10 can be connected to the communication
interface. This modem can be used for Modbus communication with a control
station, or to send error messages via SMS. In both cases, the controller can
build up a connection automatically if a fault occurs. The two functions can be
combined. In this case, an error is signalled via SMS and via Modbus.
Connection with the modem
6.4.1
A special connection line
5
(included in the scope of delivery for the modem) is
used to connect with the modem on terminals 18 to 21 of the controller base. For
this purpose, the end of the line is plugged into the controller base terminals with
the pins in such a way that the screws are visible. Then tighten the four screws in
question on the controller base.
Modbus operation via modem
6.4.2
CP02 must be set to 3 or 5. In Modbus mode, the controller accepts calls from a
control station to the modem. In the event of an error, the control station is called
on the telephone number entered at CP06.
In the case of a modem connection, before executing write commands via
Modbus, the valid code number (123) must be written to Modbus register 40145.
Otherwise, only read commands will be processed. This is used to prove the
legitimation of the control system. If an incorrect code number is entered three
times via Modbus, this is recorded as a prohibited access attempt. As a result, an
error bit is set and the control station is dialled by the controller.
Sending SMS if there is a fault on the installation
6.4.3
A modem enables the controller to send an error message to a mobile phone. As
soon as a fault is registered in the device status register of the controller, an SMS
message is sent. This requires modem access from a provider (SMSC = Short
Message Service Center) which accepts SMS messages in TAP protocol. The
message on the display of the mobile phone will then read something like this:
‚Heating controller EQJW245/device status: [XXXX]/Note: 0 = no error. >0 = error
has occurred‘
The value shown for the device status corresponds to the value of SERVice
parameter SP02. The error that has occurred is stored in this value in encoded
form (see Section 7.1.2). The SMS Center usually sends the date, time and
sender‘s telephone number for this message.
5
The line between the controller and the modem must not be longer than 1.5 m for reasons related to EMC
Summary of Contents for equitherm EQJW245
Page 2: ...2 127 www sauter controls com EQJW245 ...
Page 8: ...8 127 www sauter controls com EQJW245 ...
Page 10: ...10 127 www sauter controls com EQJW245 ...
Page 12: ...12 127 www sauter controls com EQJW245 ...
Page 54: ...54 127 www sauter controls com EQJW245 ...
Page 78: ...78 127 www sauter controls com EQJW245 ...
Page 88: ...88 127 www sauter controls com EQJW245 ...
Page 92: ...92 127 www sauter controls com EQJW245 ...
Page 102: ...102 127 www sauter controls com EQJW245 ...
Page 104: ...104 127 www sauter controls com EQJW245 ...
Page 106: ...106 127 www sauter controls com EQJW245 ...
Page 108: ...108 127 www sauter controls com EQJW245 ...
Page 110: ...110 127 www sauter controls com EQJW245 ...
Page 112: ...112 127 www sauter controls com EQJW245 ...
Page 122: ...122 127 www sauter controls com EQJW245 ...