After the cabinet is installed, it should be vertical to the ground.
When multiple cabinets are put side by side in the room, they should be aligned in a straight line, with an error less
than 5 mm.
The front/back doors of the cabinet should be properly installed. You can open and close them smoothly. The locks
should work normally, and all keys should be complete.
There should be no unnecessary formal labels inside the cabinet and on various boards.
Blank panels should be installed completely.
Fastening screws of various devices in the cabinet of the same model should be ready and tightened.
Various boards of the equipment should be installed securely, and the fastening screws on the panel should be
tightened.
All wiring inlets at the top and bottom of the cabinet should be installed with rodent-resistant nets where the seams
should be no more than 1.5 cm in diameter, to prevent rodents and other small animals from entering the cabinet.
Antistatic wrist straps should be provided in the cabinet.
Installation Steps
1)
Reserve sufficient space for front and back doors of the cabinet for maintenance.
2)
Mount the cabinet at the designed location as planned.
3)
Install the appropriate cable management bracket and cables.
4)
Install the tray and wiring layer on the rack according to the configuration of one rack with one cabinet installed or
one rack with multiple cabinets installed.
Installing Slide Rails
Before installing a slide rail, you need to have some knowledge of standard 19-inch cabinets of IEC60297. The height of
standard cabinets is measured in Rack Unit (RU, 1 RU = 44.45 mm (1.75 inch)). 1 RU is equal to the height of three holes
(see Figure 3-1). The hole in the middle is an auxiliary installation hole, and the other holes are standard installation holes.
Note that the space between neighboring standard installation holes is a little smaller than that between an auxiliary
installation hole and its neighboring standard installation hole. When installing a slide rail for the RG-S8600E series,
ensure that the plane to carry the chassis should be installed on the plane of delimiters (entire-U delimiter) of the two
neighboring RUs, as shown in Figure 3-16.
Figure 0-18 Slide Rail
Note:
and
representing entire-U delimiters
Before installing a slide rail, make sure that the weight capacity of the slide rail meets requirements.
Summary of Contents for RG-S8605E
Page 1: ...RG S8600E Series Switches Hardware Installation and Reference Guide V1 09...
Page 63: ...Figure 2 2 Preventing EMI on RG S8607E Figure 2 3 Preventing EMI on RG S8610E...
Page 86: ...Figure 3 21 Grounding Point on the Rear of the RG S8610E Switch...
Page 116: ...Figure 7 12 Replacing the Module for RG S8610E...
Page 120: ...Note A Fan modules to be removed B Fan modules to be installed...
Page 132: ......