Load Bearing Requirements
Evaluate the load bearing requirements for the ground according to the weight of the switch and its components (such as
the cabinet, chassis, module and power supply). Make sure the installation site meet the requirements.
Space Requirements
It is recommended that the width of the machine room corridor be greater than 0.8m to ensure enough space for
moving of chassis and plugging and removing of modules.
Please do not install the switch against the wall. Instead, please leave some space around the switch for heat
dissipation and switch maintenance.
Ventilation Requirements
See RG-
S8605E, RG-S8607E
and
RG-S8610E
in
Product Overview
for their heat dissipation and ventilation respectively.
Sufficient space (10 cm at least) must be reserved at the air intakes and exhaust vents for ventilation. After connecting
various cables, you should bundle the cables or place them in the cable management bracket to avoid blocking air
intakes.
Remove all foam packaging materials and protective plastics before you power on
RG-S8605E/RG-S8607E/RG-S8610E.
Temperature Requirements
To ensure the normal operation and a prolonged useful life of the RG-S8600E, you must maintain an appropriate
temperature in the equipment room. Too high or low temperature for a long period of time may damage the equipment.
In an environment with high temperature, the equipment is subjected to even greater harm, as its performance may
degrade significantly and its useful life may be shortened in the case of long-term exposure that expedites the aging
process.
Temperature Requirements of the RG-S8600E
Operating Temperature
Storage Temperature
0ºC–50ºC
-40ºC to 70ºC
The ambient temperature is measured at the point that is 1.5m above the floor and 0.4m before the
equipment when there is no protective plate in front or back of the equipment rack.
Humidity Requirements
To ensure the normal operation and a prolonged use life of the RG-S8600E, you must maintain an appropriate humidity in
the equipment room. Too high or low humidity for a long period of time may damage the equipment.
In an environment with high relative humidity, the insulating material may have bad insulation or even leak electricity,
and sometimes the materials may suffer from mechanical performance change and metallic parts may get rusted.
On the other hand, in an environment with low relative humidity, the insulating strip may dry and shrink, and static
electricity may occur easily and endanger the circuit on the equipment.
Humidity Requirements of the RG-S8600E
Operating Humidity
Storage Humidity
10% to 90% (non-condensing)
5% to 95% (non-condensing)
The ambient humidity is measured at the point that is 1.5m above the floor and 0.4m before the equipment
when there is no protective plate in front or back of the equipment rack.
Summary of Contents for RG-S8605E
Page 1: ...RG S8600E Series Switches Hardware Installation and Reference Guide V1 09...
Page 63: ...Figure 2 2 Preventing EMI on RG S8607E Figure 2 3 Preventing EMI on RG S8610E...
Page 86: ...Figure 3 21 Grounding Point on the Rear of the RG S8610E Switch...
Page 116: ...Figure 7 12 Replacing the Module for RG S8610E...
Page 120: ...Note A Fan modules to be removed B Fan modules to be installed...
Page 132: ......