![Rivacold SP Series Use And Maintenance Handbook Download Page 59](http://html.mh-extra.com/html/rivacold/sp-series/sp-series_use-and-maintenance-handbook_1465397059.webp)
ST-SP Pag.
59 Rev 02 05/13
UK
8
8
.
.
F
F
a
a
u
u
l
l
t
t
s
s
s
s
e
e
a
a
r
r
c
c
h
h
POSSIBLE CAUSES
SOLUTIONS
A
The compressor does not start and does not release a humming sound
1
Lack of voltage. Start-up relay with open contacts.
2
Thermal cut-off intervenes.
3
Loose electrical connections or incorrect electrical connections.
1
Check the line or replace the relay.
2
Re-check the electrical connections.
3
Tighten or re-do the connections in accordance to the
wiring diagram.
B
The compressor does not start (releases humming sound) and the
thermal cut-off intervenes
1 Incorrect
electrical
connections.
2
Low voltage supply to the compressor.
3
Defective start-up of the condenser.
4
Relay does not close.
5
Winding of the electrical motor interrupted or in short-circuit.
1 Re-do
the
connections.
2
Identify the cause and eliminate it .
3
Identify the cause and replace the condenser.
4
Identify the cause and replace the relay if necessary.
5 Replace
the
compressor.
C
The compressor starts but the relay does not open
1 Incorrect
electrical
connections.
2
Low voltage supply to the compressor.
3
Relay blocked in closed position.
4 Excessive
discharge
pressure.
5
Winding of the electrical motor interrupted or in short-circuit.
1
Check the electrical circuit.
2
Identify the cause and eliminate it.
3
Identify the cause and eliminate it .
4
Identify the cause and replace the relay if necessary.
5 Replace
the
compressor.
D
Intervention of the thermal cut-off
1
Low voltage supply to the compressor (imbalanced phases on tri-
phase motors).
2
Defective thermal cut-off.
3
Defective running condenser.
4 Excessive
discharge
pressure.
5
Suction pressure too high.
6
Compressor overheated, hot return gas.
7
Winding of the compressor motor in short-circuit.
1
Identify the cause and eliminate it.
2
Check its characteristics and replace it if necessary.
3
Identify the cause and eliminate it .
4
Check the ventilation and any possible restrictions or
obstructions in the system circuit.
5
Check the sizing of the system. Replace the condensing
unit with a more powerful one, if necessary.
6 Check the refrigerant load; repair the potential loss and
add gas if necessary.
If the semi-machine does not have a safety valve, the load of
refrigerant gas must be lower than 10 kg.
7 Replace
the
compressor.
E
The compressor starts and circulates, with short-spanned function cycles
1 Thermal
cut-off.
2 Thermostat.
3
Intervention of the high pressure meter, due to the insufficient
cooling of the condenser.
4
Intervention of the high pressure meter, due to the excessive load
of refrigerant gas.
5
Intervention of the low pressure meter, due to the scarce load of
refrigerant gas.
6
Intervention of the low pressure meter, due to the restriction or
clogging of the expansion valve.
1
See previous point (thermal cut-off intervention).
2
Small differential; correct adjustment .
3
Check that the motorized ventilator functions correctly or
clean the condenser.
4
Reduce the refrigerant load.
5
Repair the loss and add refrigerant gas.
If the
PARTLY COMPLETED MACHINERY
does not have a safety valve, the
load of refrigerant gas must be lower than 10 kg.
6
Replace the expansion valve.
F
The compressor functions uninterruptedly or for long periods
1
Poor load of refrigerant gas.
2
Thermostat contacts blocked in closed position.
3
System insufficiently sized in function of the load.
4
Excessive load to cool or insufficient insulation.
5
Evaporator covered with ice.
6
Restriction in the system circuit.
7 Condenser
clogged.
1
Repair the loss and add refrigerant gas.
If the
PARTLY COMPLETED MACHINERY
does not have a safety valve, the
load of refrigerant gas must be lower than 10 kg.
2 Replace
the
thermostat.
3
Replace the system with a more powerful one.
4
Reduce the load and improve insulation, if possible.
5 Defrost.
6
Identify the resistance and eliminate it .
7
Clean the condenser.
G
Running condenser damaged, interrupted, or in short-circuit
1
Incorrect running condenser.
1
Replace the condenser with the correct type.
H
Start-up relay defective or burnt out
1 Incorrect
relay.
2
Relay assembled incorrectly .
3
Incorrect running condenser.
1
Replace with the correct relay.
2
Reassemble the relay in the correct position.
3
Replace the condenser with the correct type.
I
Compartment temperature too high
1
Thermostat regulated too high.
2 Expansion
valve
under-sized.
3 Evaporator
under-sized.
4
Insufficient air circulation.
1 Regulate
correctly.
2
Replace the expansion valve with a suitable one.
3
Replace it increasing the surface of the evaporator.
4
Improve air circulation.