ST-SP Pag.
52 Rev 02 05/13
UK
Code
Level Descr.
Range
Unit
MBP LBP
HBP
List of -ALr alarm parameters
AFd
1
Temperature alarm threshold differential
This sets the re-entry temperature threshold after a high- or low-
temperature alarm condition
1.0 …
90.0
°C [°F]
2
2
2
HAL 1
Maximum
alarm
threshold
Above this value (absolute or referred to the setpoint) an alarm is
triggered
If the reference is relative, the unmarked value is added to the setpoint
-50.0 …
199.0
°C [°F]
10
10
10
LAL 1
Minimum
alarm
threshold
Below this value (absolute or referred to the setpoint) an alarm is
triggered
If the reference is relative, the unmarked value is subtracted from the
setpoint
-50.0 …
199.0
°C [°F]
-10
-10
-10
PAO
1
Temperature alarm delay at power-on
0 … 10
h
4
4
4
dAO
1
Temperature alarm delay after defrost
The time, starting from the end of the dripping phase, during which no
alarm is signalled.
In the event of contemporaneous network defrosting, the time refers to
the defrosting end command
0 … 999
min
60
60
60
OAO
1
Temperature alarm delay after door closure
The time, after the door is closed again and during which no alarm is
signalled
0 … 10
h
0
0
0
dAt
1
Defrosting alarm timeout enabling
This enables the signalling of any defrosting end due to the maximum
time limit being reached (timeout).
0 = signal disabled
1 = signal enabled
0,1 flag
0
0
0
List of -diS display parameters
ndt 1
Decimal
point
display
0 = display without decimal point
1 = display with decimal point.
0,1 flag
1
1
1
ddL
1
Display during the defrosting phase
0 = normal display (as set from the ddd par.)
1 = freezes the temperature value displayed at the start of defrosting
until the end of defrosting and the reaching of the setpoint
2 = “dF” until the end of defrosting and the reaching of the setpoint
The ddL parameter can be controlled only if the standard display (ddd
par.) includes the adjustment probe (probe 1 or network probe)
0,1,2 0
0
0
Ldd
1
Defrosting display block timeout
The time, starting from the end of defrosting (end of dripping
phase),after which the normal display is in any case restored
0 … 255
min
6
6
6
dro
1
°C or °F selection
0 = °C
1 = °F
This selection only affects temperature measurements. The values of
the parameters concerning temperature maintain their current values
and therefore, they must be varied manually to adapt them to the
Fahrenheit scale.
0,1 flag
0
0
0
List of -CnF configuration parameters
LOC
(**)
1 Keyboard
lock
0 = keyboards disabled
1 = main terminal keyboard enabled
2 = secondary terminal keyboard enabled
3 = keyboards enabled (the first to request a service has precedence
until completion)
0 … 3
1
1
1
rEL 1
Software
release
A read-only value that identifies the software version
0.0 … 99.9
-
-
-
List of -Lan(***) network parameters
dEA 1
Supervision
network
address (for Master only)
The address to be set on each master must take into account the
number of slaves present in the LAN network preceding it:
“dEA”=”dEA[previous master]”+”L01[previous master]”+1
The Supervision network address for a Slave is “dEA[master]”+”L00”)
1 … 199
1
1
1