REFUdrive 500 RD51
Basic parameterization
5-15
DOK-RD500*-RD51*******-IB01-EN-P
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0733
copy data to keypad
no
0
The complete drive converter data set is copied into the
operator panel.
0 = no
1 = yes
After the data transfer, a data set name can be entered.
You can scroll through the ASCII code using the + or - keys
(if you press the + and - key simultaneously, then you scroll
directly to the beginning of the following ranges: A, a, O and
blank). You can move the cursor to the right or left using the
< or > key.
0 / 1
0064
Parameteriz. level
pasic parametriza-
tion
2
0 = basic parametrization: The operator has access to the
pre-defined parameters of the basic parameterization.
This is either menu-prompted or via the numerical list.
1 = free parametrization: The operator can access all of
the parameters of the free parameterization.
Caution: When changing the parameterizing modes, data
may be lost! Please read Section 1.4 “Working with the basic
parameterization and the free parameterization” in the Man-
ual, Function charts and parameter list.
0 / 1
0037.00
Display line 1,2,3
f actual
0
Selecting the operating display for line 1.
0 = status (status signal from the drive converter)
1 = n actual (electrical)
2 = I active
3 = I actual (actual apparent current)
4 = U actual
5 = DC-link
6 = f actual
7 = f set
8 = P actual (actual apparent power)
9 = P active (actual active power which the motor draws)
0 ... 9
0037.01
Display line 1,2,3
f set
0
Selects the operating display for line 2.
As for parameter 0037.00.
0 ... 9
0037.02
Display line 1,2,3
status
0
Selects the operating display for line 3.
As for parameter 0037.00.
0 ... 9
0072
Source parameter
keypad, PC (RS232)
2
Specifies from which source, parameters can be set.
0 = operator panel, PC (RS232)
1 = Bus SS1
2 = Bus SS2
3 = Bus SS4
4 = Buses SS1, SS2, SS4
0 ... 4
0026
Pulse frequency
4 kHz
2
Drive converter pulse frequency
1.0 ... 12.0 kHz
Serial communications
Sub-menu to set standard RS485 interface.
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0500
SI1 protocol type
USS 4/6 words
2
The serial interface 1 (SS1) is an RS485 interface (connec-
tion X12).
0 = no protocol
1 = USS 4/2 words
2 = USS 4/6 words
3 = USS 0/2 words
0 ... 5