5-16
Basic parameterization
REFUdrive 500 RD51
DOK-RD500*-RD51*******-IB01-EN-P
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
4 = USS 0/6 words
5 = USS 4/0 words
0501
SI1 baudrate
9600 Baud
2
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud
5 = 38400 baud
6 = 76800 baud
0 ... 6
0502
SI1 parity
even
2
0 = no parity
1 = odd
2 = even
0 ... 2
0503
SI1 stop bits
1
2
Either 1 or 2 stop bits can be set.
1 ... 2
0504
SI1 slave address
0
2
The drive converter address can be set between 0 and 31 for
the RS485 bus.
Caution: There must be no two identical addresses on the
bus (each station/node must have its own unique address!
0 ... 31
0505
SI1 Rx watchdog
fault
2
0 = no reaction
1 = warning
2 = fault
0 ... 2
0506
SI1 Rx timeout
0.1 s
2
Monitoring time for the standard SS1.
If the interface does not receive an error-free protocol within
this time, then the response, selected in P0505 is initiated.
0.1 ... 60.0 s
0499
RS232 baud rate X11
9600 Baud
2
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud
5 = 38400 baud
6 = 57600 baud
7 = 76800 baud
0 ... 7
Diagnostica / drive converter data
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0028
Operating hours
0 h
-
Operating hours when the inverter is enabled.
0 ... 2147483647 h
0024
Continuous current
0025
Peak current long
0046
Peak current short
0022
Continuous ouput
0023
Peak output long
0099
Max. o/p frequency
0027
Max.normaliz. freq.
Drive converter data corresponding to the drive converter
output class
0
0001
Device ID
501
0002
Firmware version
e.g. 2
0003
Firmware module
Firmware data
e.g. 2
0006
Serial number
e.g. 3
0007
Convter number
e.g. 1
0
0008
EEPROM prog. cycles
1
-
Displays the EEPROM programming cycles
-1 ... 100000