5-4
Basic parameterization
REFUdrive 500 RD51
DOK-RD500*-RD51*******-IB01-EN-P
5.2 Password
level
The parameters are located at various access levels. A password is re-
quired to change parameters. If several parameters are changed in the
parameterization, the password must only be entered for the first. The
required password level is shown in the parameter table.
No password required.
Esc
,
Mon
,
Prog
and confirm with
Enter
.
Esc
,
Mon
,
Prog
,
and confirm with
Enter
.
All of the parameters of the lower password level are also accessible with
the selected password.
5.3 Quick-Setup
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0010
Display language
English
0
Selects the display language:
0 = German
1 = English
0 / 1
0100.00
Motor type
Asychron ASM
2
Selects the motor type:
0 = Induction motor, IM
1 = Synchronous, SM
0 / 1
0101.00
Rated speed ASM
1)
2
Rated speed from the motor rating plate. 2)
100 ... 95000 RPM
0102.00
Rated frequency ASM
1)
2
Rated frequency from the motor rating plate.
2)
10.0 Hz... P0099
0103.00
Rated current ASM
1)
2
Rated current from the motor rating plate. 2)
1.00 A... P0033
0104.00
Rated voltage ASM
1)
2
Rated voltage from the motor rating plate. 2)
10 ... 600 V
0106.00
Power factor ASM
1)
2
cos-phi from the motor rating plate. 2)
0.50 ... 0.98
0112.00
Rated current SM
1)
2
Rated current from the motor rating plate.
3)
1.00 A... P0033
0113.00
Rated speed SM
1)
2
Rated speed from the motor rating plate. 3)
100 ... 95000 RPM
0105.00
Voltage const. SM
1)
2
Voltage constant from the motor rating plate. 3)
0.01 ... 50.00 V/Hz
0107.00
Pole number SM
1)
2
Pole number from the motor rating plate. 3)
1 ... 64
0178.00
f-limit machine
50.00 Hz
2
Maximum permissible system frequency (centrifugal force
protection).
0.0 Hz ...P0027
1)
The motor data of a typical motor are set as the factory setting for every
drive converter output class.
2)
This menu item is only displayed, if an induction motor was selected as
the motor type!
3)
This menu item is only displayed, if an synchronous motor was selected
as the motor type!