REFUdrive 500 RD51
Operator control and parameterization
4-1
DOK-RD500*-RD51*******-IB01-EN-P
4
Operator control and parameterization
4.1 Operating
possibilities
he operator panel (option), the REFUwin PC and several interfaces are
available to operate, visualize and parameterize REFUdrive 500 drive
converters.
The serial RS232 and RS485 interfaces are standard on the control card.
In addition, there are the optional interface cards Profibus DP, CAN bus,
Interbus S, Peer-to-peer coupling and SynchroLink.
Fig. 4-1: Operator panel with graphic display (option)
4.2
Using the operator panel
Operating using the operator panel
The start/stop button and the plus/minus button (for the motorized poten-
tiometer function) are active when the equipment is supplied (standard
values of the basic parameterization are set).
Button
Function
Conditiones
Start
Starts the drive
Stop
Stops the drive
The on/off command must be set to "Ter-
minal, operator panel" or "Opera-
tor panel, dynamic"; refer to Section 5.4.1
Equipment control/setpoints.
Increase motorized
potentiometer setpoint
Decrease motorized
potentiometer setpoint
The setpoint must be set to "Motorized
potentiometer" and the on/off logic to
"Terminal, operator panel" or "Op-
erator panel, dynamic"; refer to Section
5.4.1 Equipment control/setpoints.
+
Changeover between
STANDARD- and TEST
mode.
Password level 2 must be entered, the
inverter
must be inhibited (refer to 4.2.2 Operating
display).
Fig. 4-2: Key functions when operating
Standard- and test mode (local / remote)
The two operating modes are used for setting-up or for service for a drive
(test mode) and for the normal mode. The on/off commands and the set-
point input can be separately set for each mode. For example, the normal
mode can be set-up for terminal operation (P0870 = static terminal), and
the test mode for operator control using the control panel (P0871 = Panel,
static).