5-6
Basic parameterization
REFUdrive 500 RD51
DOK-RD500*-RD51*******-IB01-EN-P
5.4
Guided parameterization
Device control / setpoints
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0870
on / off in NORMAL
panel static
1
Enters on/off in NORMAL operation.
0 = term.strip static (static = switch function)
1 = term.stst.+panel (term.=terminal)
2 = term.stat.+PC (PC with REFUwin via service inter-
face)
3 = term.stat.+bus SI1 (SI = serial interface)
4 = term.stat.+bus SI2 (if available)
5 = term.stat.+bus SI4 (if available)
6 = term.dyn. OFF always (dyn.=dynamic)
7 = panel dyn. OFF always
8 = term.strip dynamic (dynamic = pushbutton function)
9 = panel dynamic
10 = panel static
0...10
0871
on / off in TEST
panel static
1
Enters on/off in the TEST mode.
As for parameter 0870.
0...10
0872
setpoint in NORMAL
motor potentiome-
ter
1
Entering a setpoint in NORMAL operation
0 = motor potentiometer
1 = fix setpoint
2 = analog inp 0..±10V
3 = analog inp 0..+20mA
4 = analog inp. 4..+20mA
5 = opt. an.inp 0..±10V (Opt. = optional)
6 = opt. an.inp 0..+20mA
7 = opt. an.inp 4..+20mA
8 = PC (PC with REFUwin via service interface)
9 = bus SI1
10 = bus SI2
11 = bus SI4
12 = analog inp 2..+10V
0...12
0873
setpoint in TEST
motor potentiome-
ter
1
Enters the setpoint in the TEST mode
as for parameter 0872.
0...12
0196
Motorpot. mode
Supplementary parameter for “motorized potentiometer”.
start f-set expon.
1
For Start f-set, the last selected setpoint of the motorized
potentiometer which is selected after the off command, is
approached.
For Start f-min, the actual value f-min (P0180.XX) is ap-
proached.
In addition, the rate-of-change of the motorized potentiometer
can be set using the parameter:
linear =
uniform change according to the selected step
width
expon. =
The rate-of-change increases the longer that the
button remains pressed
0 = start f-set, linear
1 = start f-min, linear
2 = start f-set, exponential
3 = start f-min, exponential
0 ... 3
0195
Mot.pot. step value
Supplementary parameters for “motorized potentiome-
ter”.
0.01
1
The rate-of-change of the motorized potentiometer is se-
lected using the step width.
0.01 ... 10.00 Hz
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01