5-10
Basic parameterization
REFUdrive 500 RD51
DOK-RD500*-RD51*******-IB01-EN-P
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0881
function relay
O not fault
1
As for parameter 0875, from value 70 to 93.
70...93
0890
ref.-analogue outp
+10V reference outp.
1
Reference-, analog voltage
0 = +10V reference output
1 = -10V reference output.
2 = fact outp. frequency
3 = Iact outp. current (apparent current)
4 = Isq (active current)
5 = Uact outp. voltage
6 = Pact outp. power
7 = Pactiv
0...7
0221.00
PT1 filt.timeconst.
Supplementary parameter for „analog output“.
0 ms
1
To smooth any value which is connected at the analog out-
put.
0 ... 10000 ms
0559
Pactual PT1 time
Supplementary parameter for „analog output“.
50 ms
1
Only to smooth the P active value.
0 ... 10000 ms
0560
Ptrue PT1 time
Supplementary parameter for „analog output“.
50 ms
1
Only to smooth the P true value.
0 ... 10000 ms
0411
Output-block 1 sign
Supplementary parameter for „analog output“.
direct
1
Defines how a signal is transferred.
0 = direct
1 = absolute value
2 = inverted
3 = abs.value inverted
0...3
0413
Output-block 1 norm
Supplementary parameter for „analog output“.
100.00 %
1
Analog output normalization
10 V corresponds to the value set here.
6.26 ... 200.00 %
0561
Output-block
Supplementary parameter for „analog output“.
0.. ±100 %
2
0 = 0..±100 %
1 = + 20..+100 %
0 / 1
0412
Output-block 1 offs
Supplementary parameter for „analog output“.
0.00 %
1
Offset
-100.00 ... 100.00 %
Functions
•
Controller setting
•
Start/stop function
•
Thermal motor protection
•
V/Hz open-loop control
Controller setting
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0547.00
Current control Kp
0.10
1
Gain factor for the current controller.
0.01 ... 128.00
0548.00
Current control Tn
10 ms
1
Integral action time for the current controller.
0 ... 5000 ms
0532.00
Fixv. current limit
100.00 %
1
Current limiting input
100% corresponds to the contents of parameter P0374
(Factory setting: continuous output current of the drive con-
verter).
0.00 ... 199.99 %