REFUdrive 500 RD51
Description
1-3
DOK-RD500*-RD51*******-IB01-EN-P
1.3
Technical Data
Technical Data for pulse frequency f
p
= 4 kHz
RD51
1.5
3.0
4.0
5.5
7.5
011
015
018
022
030
037
Motor output
1
[kW]
1.5
3.0
4.0
5.5
7.5
11
15
18.5
22
30
37
Line supply voltage 3 AC 400 V (±15%)
Output frequency
[Hz]
0 -250 Hz
Rated current
[A]
4.0
7.5
10
13
18
25
30
35
43
56
68
Peak current for
t=60 s [A]
5.2
9.8
13
17
23
33
39
46
55
73
88
t=1 s
[A]
6.8
13
17
22
31
43
51
60
72
95
116
t=0.5 s [A]
8.0
15
20
26
36
50
60
70
85
112
136
Rated output S
N
[kVA]
2.6
4.9
6.6
8.6
12
16
20
23
28
37
45
Peak output for t=60s
[kVA]
3.4
6.5
8.6
11
15
22
26
30
36
48
58
Line supply voltage 3 AC 460 V (±15%)
Output frequency
[Hz]
0 -250 Hz
Rated current
[A]
3.5
6.5
9
12
16
21
27
31
38
49
60
Peak current for
t=60 s [A]
5.2
9.8
13
17
23
33
39
46
55
73
88
t=1 s
[A]
6.8
13
17
22
31
43
51
60
72
95
116
t=0.5 s [A]
8.0
15
20
26
36
50
60
70
85
112
136
Rated output S
N
[kVA]
2.6
4.9
6.6
8.6
12
16
20
23
28
37
45
Peak output for t=60s
[kVA]
3.4
6.5
8.6
11
15
22
26
30
36
48
58
Line supply voltage 3 AC 500 V (+10% / -15%)
Output frequency
[Hz]
0 - 250 Hz
Rated current
[A]
3
6
8
10
14
20
24
28
34
45
54
Peak current for
t=60 s [A]
3.9
7.8
10
13
18
26
31
36
44
59
70
t=1 s
[A]
5.1
10
14
17
24
34
41
48
58
77
92
t=0.5 s [A]
6.0
12
16
20
28
40
48
56
68
90
108
Rated output S
N
[kVA]
2.5
4.9
6.6
8.2
12
16
20
23
28
37
44
Peak output for t=60s
[kVA]
3.2
6.4
8.2
11
15
21
26
30
36
49
58
Ambient conditions, radio interference suppression level, noise immunity
Environmental class
3K3 according to DIN IEC 721-3-3 (ambient temperature 0-40 °C)
Cooling airflow requirement [m³/s]
0.02
0.02
0.02
0.03
0.03
0.05
0.05
0.05
0.1
0.1
0.2
Radio interference suppression level/ noise immunity A 1 according to EN 55011 / EN 61800-3
Mechanical design
Size classes
A
A
A
A
A
B
B
B
C
C
C
Degree of protection
IP 20 according to EN 60529
IP 20 acc. to EN 60529 (without terminal
connections)
Weight of the drive converter for cooling type
Forced ventilation
[kg]
15
15
15
15
15
18
18
18
33
33
33
Liquid cooling
[kg]
10
10
10
10
10
12
12
12
25
25
25
Heat conducting plate
[kg]
10
10
10
10
10
12
12
12
--
--
--
Brake resistor
Continuous braking power
2
[kW]
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.4
0.4
0.4
1
Maximum permissible motor output referred to a 4-pole standard induc-
tion motor.
2
When the braking resistors are mounted in the air flow.
LSA Control S.L. www.lsa-control.com [email protected] (+34) 960 62 43 01