Product designation
3-30
PHOENIX CONTACT
6874_en_16
The following states can be displayed under "Transceiver status":
–
"System Hardware does not support diagnosable POF modules" (this hardware does
not support POF-SCRJ diagnostics)
–
"No POF-SCRJ Interface modules present" (no POF-SCRJ module is plugged in)
–
"POF-SCRJ Interface module is present and OK" (the system reserve is greater than
2 dB and is displayed under "RX system reserve")
–
"POF-SCRJ Interface module is present, but the system reserve is low" (the system
reserve is less than 2 dB, but greater than 0 dB)
–
"POF-SCRJ Interface module is present, but the system reserve is exhausted" (no
system reserve available - the received optical power is below the required minimum
value)
The actual value of the system reserve can read by the Profinet engeneering and also be
used for Profinet alarms.