The Modular Managed Switch System (MMS) and the Managed Compact Switch (MCS)
6874_en_16
PHOENIX CONTACT
1-17
bF
System bus error
(Bus Fail)
–
Make sure that the extension modules are plugged in correctly.
–
Restart the switch.
Po
Power
–
Power over Ethernet monitoring has been activated on at least
one port and an error has occurred. Check the physical
connection at the PoE ports and the settings in WBM.
HS
Hardware support
–
At least one interface module is inserted in the MMS that is not
fully supported by the MMS hardware version used. The
interface module transmits data, the management functions
are deactivated. The message appears for approximately ten
seconds on the display after a restart or after interface modules
have been inserted or removed. The interface module can be
used in unmanaged mode.
LF
Loop Failure - the redundant ring
has been interrupted
–
The redundant ring has been physically interrupted. Check the
physical connection.
–
The switch configured as the redundancy manager did not find
a valid MRP module on the last device startup, there is no
redundant connection. Make sure that at least one switch is
configured in the MRP ring as the MRP manager
and a valid
MRP module is plugged in
.
–
Incorrect ports. Make sure that the MRP ring is only created via
ports that are configured as an MRP port.
–
Unsuitable switches. Make sure that all the switches that form
the MRP ring support MRP.