Product designation
12-8
PHOENIX CONTACT
6874_en_16
12.2
Typical current consumption (MMS) - (Example)
Typical module current consumption
FL SWITCH MM HS [1]
350 mA
FL MXT [2]
250 mA
FL IF 2TX VS-RJ ... [3]
0 mA
FL IF 2HCS 100 ... [4]
100 mA
FL IF 2FX (SM) SC or ST ... [5] including the following revisions:
FL IF 2FX SC-D, HW: 00 to 04,
FL IF 2FX SM SC-D,HW: 00 to 02,
FL IF 2FX ST-D, HW: 00
200 mA
FL IF 2FX (SM) SC or ST ... [5] from following revisions:
FL IF 2FX SC-D, HW: 05,
FL IF 2FX SM SC-D,HW: 03,
FL IF 2FX ST-D, HW: 01
200 mA
FL IF TX/POF 10/100 ... [6]
60 mA
FL IF TX/HCS 100 ... [7]
60 mA
FL IF MEM ... [8]
0 mA
FL IF 2PSE ...
30 mA (from MMS, additional 850 mA, maximum from external 48 V PoE
supply)
FL IF 2POF SCRJ-D
200 mA
Example structures
Station with 2 FX modules and 2 TX modules
350 mA [1] + (2 x 200 mA [5]) + (2 x 0 mA [3]) = 750 mA
Station with 2 FX modules, 5 HCS modules, and 1 POF/TX module
350 mA [1] + 250 mA [2] + (2 x 200 mA [5]) + (5 x 100 mA [4]) + 60 mA [6] = 1560 mA
Station with 5 FX modules, 4 HCS modules, 2 TX modules, and 1 POF/TX module
350 mA [1] + (2 x 250 mA [2]) + (5 x 200 mA [5]) + (4 x 100 mA [4]) + (2 x 0 mA [3]) + 60 mA [6] = 2310 mA