One or more interface modules configured incorrectly -> Following startup, the
MMS/MCS indicates "Cd" (configuration difference) in the display
9.2.2
Configuring the switch as a PROFINET IO device
Once all switches have been added to the bus configuration, the following settings must be
made for the individual switches via the "Detail View" tab (device details):
–
The PROFINET device name must be checked and modified, if necessary.
–
The IP address and the subnet mask must be checked and modified, if necessary.
–
The update time for inputs should be set to
"512 ms"
(default).
–
The update time for outputs should be set to
"512 ms"
(default).
–
The monitoring time should be set to
"2000 ms"
(default).
–
The interface modules must be selected from the module catalog and added to the
station.
Figure 9-3
Device details with modified settings
The PROFINET variables can then be created and used in the control program.
If "Cd" appears in the display, insert the correct interface modules and restart the switch.
The desired/actual configuration is no longer monitored during the system runtime.
Set by the user:
Station name
IP address
Subnet mask
Recommended value