Possible Reason for Trip
22 10V FAULT
10V fault:
•
+10V REF overload warning (terminal 4) -
10mA maximum
25 DC LINK RIPPLE
The dc link ripple voltage is too high:
•
Check for a missing input phase
27 OVERSPEED
Overspeed:
•
>150% base speed when in Sensorless Vector mode
28 ANOUT FAULT
AOUT overload on terminal 5:
•
10mA maximum
29 DIGIO 1 (T9) FAULT
DIN3 overload on terminal 9:
•
20mA maximum
30 DIGIO 2 (T10) FAULT
DOUT2 overload on terminal 10:
•
50mA maximum
31 UNKNOWN
Unknown trip
32 OTHER
"OTHER" trip is active (Trip ID 34 to 44 inclusive)
- Product Code Error
Switch unit off/on. If persistent, return unit to factory
- Calibration Data Error
Switch unit off/on. If persistent, return unit to factory
- Configuration Data Error
Press the
key to accept the default configuration. If persistent, return unit to
factory