Programming Your Application
6-11
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SKIP FREQUENCY
BAND 1
The width of skip band 1 in Hz
0.0 to 60.0 Hz
0.0
SKIP FREQUENCY 2 This parameter contains the centre frequency of skip band 2 in Hz
0.0 to 240.0 Hz
0.0
SKIP FREQUENCY
BAND 2
The width of skip band 2 in Hz
0.0 to 60.0 Hz
0.0
AUTO RESTART
ATTEMPTS
Determines the number of restarts that will be permitted before requiring
an external fault reset
0 to 10
0
AUTO RESTART
DELAY
Determines the delay between restart attempts for a trip included in
AUTO RESTART TRIGGERS and AUTO RESTART T. The delay
is measured from all error conditions clearing
0.0 to 600.0 s
10.0
AUTO RESTART
TRIGGERS
Allows Auto Restart to be enabled for a selection of trip conditions.
Refer to Chapter 7: "Trips and Fault Finding" - Hexadecimal
Representation of Trips
0x0000 to 0xFFFF
0x0000
AUTO RESTART
T
Allows Auto Restart to be enabled for a selection of trip conditions.
Refer to Chapter 7: "Trips and Fault Finding" - Hexadecimal
Representation of Trips
0x0000 to 0xFFFF
0x0000
DB ENABLE
Enables operation of the dynamic braking.
0=FALSE
1=TRUE
1
DB RESISTANCE
The value of the load resistance.
1 to 1000
product
code
dependent
DB POWER
The power that the load resistance may continually dissipate.
0.1 to 510.0 kW
product
code
dependent
DB OVER-RATING
Multiplier that may be applied to DB POWER for power overloads lasting
no more than 1 second.
1 to 40
25
LOCAL MIN SPEED
F
The magnitude of the minimum setpoint that will be used when running
in Local Mode.
0.0 to 100.0 %
0.0 %
ENABLED KEYS
F
The following keys on the 6901 keypad can be enabled or disabled
separately. The combination produces the parameter setting as in the
table below. The default of FFFF enables all keys.
0000 to FFFF
FFFF