Installing the Drive
3-3
650S AC Drive
Mounting the Drive
To maintain compliance with European Electrical Safety Standard VDE0160/EN50178 the unit
must be mounted inside a control cubicle that requires a tool for opening. The cubicle should
provide 15dB attenuation to radiated emissions between 30-100MHz.
M
ount the drive
vertically
on a solid, flat, non-flammable, vertical surface. It can be panel-
mounted, or rail-mounted on a rail complying with EN50022 (35mm DIN).
DIN Mounting
To DIN mount the unit, hang the unit on the top DIN rail and push the unit onto the bottom DIN rail
until it snaps in to position. Secure with a lower screw fixing. To release the unit, use a flat bladed screwdriver as shown.
Ventilation
Maintain a minimum air clearance for ventilation of 100mm (4 inches) above and below the unit. When mounting two or
more 650S units together, these clearances are additive. Ensure that the mounting surface is normally cool. Be aware that
adjacent equipment may generate heat and also have clearance requirements. Provided the minimum clearance for ventilation
is maintained, 650S drives may be mounted side-by-side.
lower
fixing
hole