Programming Your Application
6-27
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::FLY Menu
VECTOR ENABLE
This parameter is used to indicate whether or not the speed search is on
the way.
TRUE : The drive is searching for the actual motor speed.
FALSE : The drive is running a standard mode
0=FALSE
1=TRUE
0
ACTIVE
This parameter is used to indicate the speed in electrical Hertz that was
found during the preceding flycatching search.
0=FALSE
1=TRUE
SETPOINT
This parameter is used to enable/disable the fly-catching feature.
TRUE : Fly-catching is enabled. The motor will search the rotating speed
at each torque switch on and start to control the motor from this speed.
FALSE : Fly-catching is disabled. The motor will start to control the motor
based on an initial zero speed at each torque switch on.
-32768 to 32768
PAR Menu
APPLICATION
This parameter selects and loads the Application to be used. APP 0 will
not control a motor. APP 6, 7 & 8 are for future use. You can edit an
Application in DSELite and, then set this parameter to CUSTOM to
produce your own custom Application.
Refer to the 650S Software Product Manual, Chapter 5: "Applications"
which gives detailed information about each Application.
Note:
Parameter values are changed to factory settings
by loading a new Application, except Motor
Parameters (indicated
M
)
0= NULL
1= STANDARD
2= LOCAL/REM
(AUTO/MANUAL)
3= PRESETS
4= RAISE/LOWER
5= PID
6= APP 6
7= APP 7
8= APP 8
9= CUSTOM
1
MAX SPEED
M
The frequency at which the 650V will run when maximum setpoint is
applied. The default is Product Code dependent
7.5 to 300Hz
50 or
60Hz
MIN SPEED
The minimum frequency at which the 650V will run, as a percentage of
the MAX SPEED parameter
-100.0 to 100.0%
0.0%
ACCEL TIME
The time taken for the 650V output frequency to ramp up from zero to
MAX SPEED
0.0 to 3000.0s
10.0s
DECEL TIME
The time taken for the 650V output frequency to ramp down from MAX
SPEED to zero
0.0 to 3000.0s
10.0s
JOG SETPOINT
Speed the 650V will run at if the Jog input is high, as a percentage of
the MAX SPEED parameter
-100.0 to 100.0%
10.0%