Programming Your Application
6-9
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
AOUT 2 SOURCE
F
0 : NONE
1 : DEMAND
2 : CURRENT
3 : PID ERROR
4 : RAISE/LOWER
0 : NONE
SET::TRIP Menu
DISABLE LOOP
Disables LOST I LOOP trip (4-20mA)
0= TRIP ENABLED
1= TRIP DISABLED
1
AIN2 OVERLOAD
Disables the overload trip (Terminal 3)
As
S
LOOP 0
DISABLE STALL
Disables STALL trip
As
S
LOOP 0
DISABLE MOTOR
OVERTEMP
Disables the motor thermistor trip
As
S
LOOP 0
INVERSE TIME
Disables the inverse time trip
As
S
LOOP 1
DYNAMIC BRAKE
RESISTOR
Disables the dynamic brake resistor trip
As
S
LOOP 1
DYNAMIC BRAKE
SWITCH
Disables the dynamic brake switch trip
As
S
LOOP 1
SPEED FEEDBACK
Disables the speed feedback trip
As
S
LOOP 0
OVERSPEED
Disables the overspeed trip
As
S
LOOP 0
DISPLAY (KEYPAD)
Disables the display (keypad) trip
As
S
LOOP 0
DC LINK RIPPLE
F
Disables the DC link ripple trip
As
S
LOOP 0
SET::SERL Menu
REMOTE COMMS
SEL
F
Selects the type of remote communications mode:
0 : FALSE, and in REMOTE mode then control is from the terminals.
1 : TRUE, and in REMOTE mode then control is from the
communications.
0=FALSE
1=TRUE
0
COMMS TIMEOUT
F
Se
ts the maximum time allowed between refreshing the COMMS
COMMAND parameter. The drive will trip if this time is exceeded. Set
the time to 0.00 seconds to disable this feature.
0.0 to 600.0s
0.0s
COMMS ADDRESS
F
The drives identity address.
Note: if set to 0, it will only respond to broadcast messages.
0 to 255
0