![Parker 650S Series Product Manual Download Page 56](http://html.mh-extra.com/html/parker/650s-series/650s-series_product-manual_755635056.webp)
Programming Your Application
6-5
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::CTRL Menu
POS TORQUE LIMIT
This parameter sets the maximum allowed level of positive motor torque. -500.0 to 500.0%
200.0%
NEG TORQUE LIMIT
This parameter sets the maximum allowed level of negative motor
torque.
-500.0 to 500.0%
-200.0%
STALL TRIP TYPE
F
This parameter determines whether the stall trip operates on motor
torque or motor current.
FALSE = TORQUE, TRUE = CURRENT
0= FALSE
1= TRUE
1
SPEED PROP GAIN
F
M
Sets the proportional gain of the loop.
Speed error (revolutions per second) x proportional gain = torque
percent.
0.00 to 300.00
product
code
dependent
SPEED INT TIME
F
M
This is the integral time constant of the speed loop. A speed error which
causes the proportional term to produce a torque demand T, will cause
the integral term to also ramp up to a torque demand T after a time
equal to “speed int time”.
1 to 15000ms
product
code
dependent
SPEED POS LIMIT
F
This sets the upper limit of the speed demand.
-110.00 to 110.00% 110.00%
SPEED NEG LIMIT
F
This sets the lower limit of the speed demand.
-110.00 to 110.00% -110.00%
SET::IN Menu
DIN 1 INVERT
Inverts the value of the signal, TRUE or FALSE.
0= FALSE
1= TRUE
0
DIN 2 INVERT
As
S
IP01 As
S
IP01 0
DIN 3 INVERT
As
S
IP01 As
S
IP01 0
DIN 4 INVERT
As
S
IP01
As
S
IP01 0
DIN 5 INVERT
As
S
IP01
As
S
IP01 1
DIN 6 INVERT
As
S
IP01
As
S
IP01 0
DIN 7 INVERT
As
S
IP01
As
S
IP01 0
AIN 1 SCALE
-300.0 to 300.0%
100.0%
AIN 1 OFFSET
-300.0 to 300.0%
0.0%
AIN 1 TYPE
VALUE
+
SCALE
OFFSET
X
INPUT
TYPE
UNPROCESSED
0 to 100% of selected TYPE
0= 0-10V
1= 0-5V
0