6-30
Programming Your Application
650S AC Drive
Configuring Terminals 9 & 10 (Digital Input/Output)
Terminal 10 can be operated as digital input DIN 4 or digital output DOUT2. It is configured via the keypad or ConfigEd Lite
(or other suitable programming tool). The default for terminal 10 is to operate as a digital input, and the input logic is non-
inverted.
Terminal 9 can be operated as digital input DIN3 or digital output DOUT1, however, it can only be configured via ConfigEd
Lite (or other suitable programming tool). The default for terminal 9 is to operate as a digital input, and the input logic is non-
inverted.
Configure for use as a Digital Input (default)
For example, to use terminal 10 as an input, the output circuitry must be disabled by setting DOUT 2 SOURCE and DOUT 2
INVERT to zero. You can invert this logic using parameter DIN 4 INVERT.
Parameter
Setting
DOUT2 SOURCE
0
DOUT2 INVERT
0
DIN4 INVERT
Default is 0, setting to 1 inverts the input logic